I. Overview
The TDS-2000 distributed control system is a high-performance control system that integrates computer technology, conversion technology, graphic display technology, remote communication technology, and high-speed network technology. It is suitable for automation process control systems in large, medium, and small-scale hydropower plant factories and can be widely applied to control systems ranging from several circuits to thousands of circuits. The system retains the intuitiveness of on-site digital instrument monitoring, realizes dual insurance of microcomputer and instrument control, and has good practicality, especially suitable for small and medium-sized hydropower stations.
2、 System configuration
1. System architecture
A、 Tree root type (based on RS232).
B、 Bus type (based on RS422, RS485).
2. Supporting instruments: Our factory's intelligent digital instruments.
3. System software:
Development platforms: Windows 2000/XP/2003, Windows NT, Windows 7.
Development languages: VB6.0, VC++6.0, JAVA.
Module structure: Communication module, flowchart module, history module, adjustment module, alarm module, grouping control module, trend module, system optimization module, report module, driver library.
System development software: TDS2000A.
System operating software: TDS2000B.
4. Network system: The TDS2000 system is a workstation that supports multi machine networks.
5. Support remote real-time control.
6. Wireless transmission requires configuration: GPRS wireless transmission module and fixed IP address.
3、 System functions
(1) Operation station function
1. Overall performance
Each station can be connected to 64 control units or acquisition units, with up to 128 control points and 2048 measurement points. The TDS-2000 system has a good human-machine interface, excellent process control, regulation, data processing, and graphic display. It can be connected to intelligent digital instruments, various domestic and foreign intelligent instruments, and PLC equipment produced by our factory, forming a complete, practical, and safe TDS-2000 distributed control system. The TDS-2000 system has comprehensive graphic, display, reporting, adjustment, trend, and other functions.
2. Communication
High speed serial or multi serial communication is used between the operation station and the adapter. The transmission distance shall not exceed 20 meters. The adapter to the instrument adopts RS485 bus network type or RS232 one-to-one corresponding radiation type. The transmission distance shall not exceed 1500 meters.
3. Operation station function
1) Overall interface: The overall interface provides the operator with a macro interface to observe objects from an overall perspective. The operator can simultaneously observe up to 28 display blocks within one interface, which can be work blocks, 8 or 16 workstation control groups, whole or process diagrams, or explanatory annotation blocks. The block functions can be accessed using shortcut keys or a mouse.
2) Process interface: The process interface has 128 pages and can display real-time process parameters of process detection points and control points. It can monitor temperature, pressure, flow rate, switch points, valve opening, etc. in real time.
3) Control group interface: The control group interface provides interfaces for 8 closely related circuits for operation. Each interface displays the measured values, given values, output valve position values, circuit operation status, etc. of 8 workstations using instrument charts and numbers. At the same time, operations can be performed on the given values, output values, and circuit operation status of each workstation.
4) Adjustment interface: The adjustment interface provides users with a detailed adjustment interface, allowing them to observe and operate changes in a workstation. Displaying and setting the measurement values, setpoint values, output valve position values, and other adjustment parameters of the circuit, as well as displaying the instrument chart and real-time adjustment trend chart, is a very practical interface for adjusting PID parameters and observing the adjustment effect.
5) Alarm interface: Each interface can display the alarm status of 20 circuits, and up to 16 interfaces can record the alarm status of 320 circuits.
6) Trend interface: Trend curves can be divided into three types: real-time trend, historical trend, and batch trend. The trend interface can display up to 8 trend curves per page, with a total of 112 pages, including 16 pages for real-time trends, 64 pages for historical trends, and 32 pages for batch trends. On one interface, multiple strokes can be displayed simultaneously, or one stroke can be selected to be displayed separately.
7) Reports: Reports can be formatted by users and can include real-time printing, shift reports, daily reports, and monthly reports.
8) System configuration: The TDS-2000A configuration system provides a complete installation and combination of various functions for the TDS-2000B operating system. This includes basic configuration, overall configuration, flowchart configuration, group control configuration, adjustment interface configuration, trend interface configuration, report, alarm configuration and registration, etc.
(2) Network function
1. Configure network components
Windows provides very comprehensive and flexible network functionality, supporting multiple network environments. Network installation includes hardware installation and software installation. Before installing network software, it is necessary to ensure that the network hardware (including network cards, cables, and other devices) has been installed. If Windows does not provide a network password when starting, or if there is no "Network Neighborhood" icon on the desktop, it means that the correct network components have not been installed yet.
2. Resource sharing
Windows provides two levels of resource sharing control methods: global resource sharing and individual resource sharing.
3. Remote real-time monitoring and status inquiry.
4. Provide interconnection of various throttling points (via LAN).
(3) Wireless transmission function
1. Wireless transmission mode
The GPRS module is matched with our intelligent digital instrument to transmit data to the target computer through wireless network, which can achieve data monitoring in remote areas and save manpower and material resources.
2. Basic configuration
Our factory has intelligent digital instruments and GPRS modules.
3. Using TCP network protocol and supporting sending data in SMS format to 1-5 numbers, with the option to freely set the sending time interval.
4. Scope of application
Remote meter reading, remote reservoir location transmission, and the distance between the reservoir and the monitoring room.