I. Overview

The TDS-04300 series dry-type transformer temperature monitoring and control device is a control apparatus designed to ensure the safe operation of dry-type transformers. Featuring a novel design, this device incorporates comprehensive system self-check, system protection, parameter storage, and output functions.

1. The circulating display of three-phase winding temperatures or the tracking display of the highest temperature phase winding (switchable at will).

2. Implement automatic or manual control (switchable at will) for the start-stop operation of the cooling fan.

3. Display, alarm, and output of sensor open circuit, fan failure, and system fault self-test signals.  

4. The black box function can save all monitoring parameters before a power outage for future reference.

5. Independent temperature indication zero point and proportional compensation for each phase winding.

6. Output three independent 4~20mA analog signals corresponding to the A, B, and C phase windings, along with RS485, RS232, and RS422 communication functions.

II. Technical Specifications

The temperature controller is designed in accordance with the JB/T 7631-94 standard "Resistance Thermometers for Transformers."

2. Usage Conditions: Ambient Temperature: -20 to 55°C Relative Humidity <85%

Power supply voltage: 380V (three-phase) 220V (single-phase) 50±2Hz

3. Inspection routes: 4 routes, with three measuring phases A, B, and C, and one measuring ambient temperature

4. Measurement range: 0.0 to 200.0°C (sensor Pt100)

5. Measurement accuracy:  

General type: Class 0.5 ±1 digit  

Resolution: 0.1°C

6. Display mode: The left 1 digit shows the inspection route number; the middle 4 digits display the measured value; the right 1 digit indicates the alarm route number

7. Anti-interference Performance: For common-mode interference voltage of 250V (AC, 50Hz) or differential-mode interference voltage of 200mV (AC, 50Hz), the display value variation shall be less than the basic error value

8. Display value compensation range: 0~±19.9°C

9. Alarm and Protection Functions: Sensor open circuit alarm/instrument fault self-test alarm/input over-range self-test alarm/fan failure alarm

10. Relay contact output: Contact capacity 15A/250VAC, three-phase with two sets

11. External dimensions: 160×80×130mm (height×width×depth)  

Mounting dimensions: 152×76mm