1. Connect A to A1~A12, B to B1~B12, and C to C1~C2 of the 1-12 resistance sensors
2. 1-12 thermocouples, standard signals, A connected to A1~A12, B connected to B1~B12
3. The 12 channels and 12 sensors must be in a three wire system. If there are two wires, they must be connected together. A, B, and C wires, with 12 wires each, must be connected to the input end of the instrument cabinet. The C wire output (connected to the instrument) of the instrument cabinet wiring board can be connected in parallel to form one channel, with 6 copper core wires of 0.5-1mm2 connected to instruments C1 and C2
The external dimensions are 160 × 80 × 130mm, and the wiring is shown in Figures 3 and 4. The wiring instructions are the same as those in Figures 2 and 3 of TDS-0800
The external dimensions are 160 × 80 × 250, and the wiring is shown in Figure 2. The wiring instructions are as follows:
1. HHI: Upper limit alarm, connected to normally open terminals (9) and (10)
2. HI: Upper limit alarm, connected to normally open terminals (6) and (7)
3. LI: Lower limit alarm, connected to normally open terminals (9) and (10)
4. BL: Resistance or couple breaking alarm, separate relay connected to normally open terminals (16) and (17); Dual relays and HI share a set of terminals
5. RS485 communication interface: A terminal (11), B terminal (12), ground terminal (13)
6. RS422 communication interface: receive terminal A (1), receive terminal B (2), send terminal A (3), receive terminal B (4)
7. Working power supply: Connect terminals (18) and (20)
8. Hole size: 152 × 76mm