3.2 TDS-0800 Digital Temperature Inspection and Control Instrument

Column:Selection Guide Time:2026-11-09
shared:

image.png

3. 8 channels and 8 sensors must be in a three wire system. If there are two wires, they must be connected to three wires A, B, and C. All 8 wires of A, B, and C must be connected to the input end of the instrument cabinet. The C wire output of the instrument cabinet wiring board (connected to the instrument) can be connected in parallel with 4 channels to form one channel, and connected to the C end of the instrument with 2 copper core wires of 0.5~1mm2

Wiring instructions for Figures 2 and 3

1. HHI: Upper limit, connected to normally open terminals (14) and (15)

2. HI: Upper limit, connected to normally open terminals (20) and (21)

3. LI: Lower limit, connected to normally open terminals (17) and (18) in the double upper and double lower limit meter; Connect normally open terminals (14) and (15) in the upper and lower limit table

4. S or LLI: Power off/lower limit, connected to normally open terminals (5) and (6)

5. BL: Resistance or couple breaking alarm, separate relay meter connected to normally open terminals (17), (18), dual relay meter and HI shared (20), (21)

6. RS485: A terminal (7), B terminal (8), ground terminal (9)

7. RS422: Receive A terminal (9) and B terminal (10), send A terminal (11) and B terminal (12)

8. The wiring of (17) and (18), A1~A8, and B1~B8 of the 8-way C-line terminal in Figure 4 is shown in the figure

Connect HI to normally open terminals (21) and (22); HHI connected to normally open terminals (15) and (16)

9. Working power supply: Connect terminals (22) and (24); Figure 4 Connecting terminals (23) and (24)