I. Overview
The TDS-3B390 and TDS-3B290 instruments, along with copper and platinum resistance sensors, form a transformer temperature measurement and control instrument. The instrument contains three sets of control relay outputs, which can be used to start and stop the transformer cooling system, signal alarms, and drive the cooling system to control the temperature rise of the transformer. RS485 or 4-20mA signals are used for synchronous display of secondary digital instruments or computer monitoring systems in the central control room.
2、 Main technical indicators
1. Environmental temperature: -20 ℃~50 ℃, relative humidity ≤ 85%; Altitude: ≤ 2000 meters
2. Working power supply: AC/DC 100V~220V; 50Hz
3. Display range: 0.0~150.0 ℃; Basic error: ≤± 0.5% ± 1 word
4. Control settings: keyboard numeric settings; Control sensitivity: ± 1 word; Control error: ± 1 word
5. Output mode: Relay contact capacity: 220V AC, 3A
Analog output D/A: 4~20mA (load resistance ≤ 750 Ω) (optional)
Communication function Modbus RTURS485 or RS422, RS232 (optional)
6. Display mode: "H-A" is displayed when exceeding 10% of the upper range, and "L-A" is displayed when exceeding 10% of the lower range,
Display "A-A" when resistance or coupling is broken
7. The outer dimensions of the instrument protection cover are as follows: 320 × 240 × 160mm (height × width × thickness);
Weight of instrument protection cover: 2kg
8. Installation type: hanging type
Example of Instrument Model
TDS-3B20、TDS-3B37、TDS-3BPC3、TDS-3B69