0598-8241694

2.2 TDS-3W000 Universal Intelligent Digital Measurement and Control Instrument

Column:Selection Guide Time:2026-11-10
shared:

I. Overview

The TDS-3W000 universal intelligent digital measurement and control instrument adopts the latest jumper free technology. By simply setting the instrument parameters, the input signal type of the instrument can be changed to achieve universal division number input.

Features:

1. The power station mainly uses three types of signals: platinum resistance Pt100, copper resistance Cu50, and G53, which can be freely selected on the instrument.

2. The automatic zero calibration system overcomes the zero drift caused by environmental temperature changes.

3. The communication and analog output adopt optoelectronic isolation, which enhances the stability of the instrument.

4. Intelligent digital calibration, set parameter password lock, can be permanently saved after power failure.

5. Equipped with a dedicated hardware watchdog chip, it has strong anti-interference ability and can set the input filtering depth and range by itself. It also has an automatic reset function.

2、 Main technical parameters

1. Usage environment: Environmental temperature 0-50 ℃, relative humidity ≤ 85% RH · Avoid strong corrosive gases

2. Working power supply: Linear power supply: AC220V ± 15%, 50Hz ± 5Hz

Switching power supply: AC/DC100~220V ± 20%;

3. Input signal: Thermocouple: Standard thermocouples - B, S, K, E, J, T, WRe, etc

Thermal resistance: standard thermal resistance - Pt100, Pt100.1, Cu50, etc. or remote pressure resistance

Current: 0-10mA, 4-20mA, etc. - Input impedance ≤ 250 Ω

Voltage: 0-5V, 1-5V, mV, etc. - Input impedance ≥ 250k Ω

4. Measurement range: 0~100 ℃, -50~100 ℃, -50~150 ℃, -1999~9999 words

5. Measurement accuracy: 0.5% FS ± 1 word

6. Resolution: 0.1 words

7. Display format: Single screen: 4-digit 0.8 "LED red

8. Output signal: Analog output DC0-10mA (load resistance ≤ 750 Ω)

DC4-20mA (load resistance ≤ 500 Ω)

DC0-5V (output resistance ≤ 250 Ω)

DC1-5V (output resistance ≤ 250 Ω)

Switching output contact capacity: AC220V/3A

Communication output optoelectronic isolation RS485, RS422, RS232 interfaces, Modbus protocol

9. Parameter setting: panel touch sensitive button numerical setting, parameter setting value permanently saved after power failure, parameter setting value password locked

10. Power consumption: ≤ 5W

11. Dimensions: 160 x 80 x 130mm, hole size: 152 x 76mm

12. Installation form: dashboard mounted, horizontal

13. Weight: 500g